ADP-1103-TW5 – Installation Instructions


Installation Instructions – Printer friendly (pdf)

ADP-1103-TW5 – Information Page


Installation Instructions for HMI HOYME Adaptor 1103-TW5

24/120Vac Controlled Line Voltage to Switch 24Vac

Hoyme-Yellow-Box-csa2
  • 4” x 5” x 2 1/2” (101 x 127 x 64 mm)
  • ADP-1102-TWP – Interface Relay Adaptor
  • This Adaptor ADP-1103-TW5 is an automatic control switch which is designed but not limited to accommodate two separate exhaust fans in a dwelling having one furnace and (if used) a replacement air damper. A controlled 120Vac signal from one exhaust fan and/or a 24Vac signal (or dry contacts) from a second exhaust fan will simultaneously turn on the furnace circulation fan and open the replacement air damper. Added is a relay to also open the damper during furnace firing
image-2

Installation Of This Adaptor Shall Be In Accordance With The Requirements Of the Authorities Having Jurisdiction.

Refer also to HOYME Installation Instructions: Combustion Inlet Air Control Damper, Series HOM; Replacement/Ventilation Air Control Damper – HAC-0x10-OPC/PO; ADP-1101-05; ADP-1102-TWP, ADP-1103-TWP and ADP-1102-TW5.

Fitness of this Adaptor/Damper combination to satisfy air supply requirements for fuel fired appliances during operation of the in­terconnected exhaust fan(s) shall be investigated by the enforcing authorities.

Air Intake Duct Installation shall be in accordance with: In Canada – CAN/CSA B149 & B139; In the USA – ANSI/NFPA 54, 2006, ANSI Z223.1 and/or local codes including local codes relating to ventilation air duct installation.

  • I.D.: ADP -1103 – TW5
    • One Relay DPDT: Relay Coil -120Vac
    • One Relay SPDT: Relay Coil – 24Vac
    • One Relay DPDT: Relay Coil – 24Vac
    • All Contact Points – 24Vac – 5Amps

Requirements

  • Adaptor line voltage leads, connected to the 120Vac Exhaust Fan controlled line, shall be suitably cabled, fastened and enclosed in suitable raceways
  • Always refer to local and applicable codes
  • Always conduct a thorough check-out after installation is complete
  • Affix appropriate labels and follow instructions and warnings on each label

Instructions

Connecting the Adaptor ADP-1103-TW5 to a controlled 120Vac Designated Ventilation Exhaust Fan and heating appliance.

  • Turn off electrical power supply to both the Exhaust Fan and furnace circuits
  • Connect the controlled 120Vac Exhaust Fan Circuit to the Black and White adaptor leads as per wiring dia­gram. Follow applicable codes
  • Connect Adaptor terminal #5 to the Furnace Terminal ‘R’ (24 Vac)
    • (a) Disconnect the thermostat wire ‘G’ (if used) from the Furnace Terminal ‘G’ and connect it to the Adaptor Terminal #3(GT)
    • (b) Connect Adaptor Terminal #4(GF) to the Furnace ‘G’
  • Turn on the power supply to both the Furnace and to the Exhaust Fan. Turn on the Exhaust Fan which will simultaneously turn on the Furnace Circulation Fan

Connecting an Exhaust Fan with (a) controlled 2C-24Vac signal or (b) using dry contacts, to connect to the Adaptor 1103-TW5

  1. Turn off the power supply to both the furnace and the Exhaust Fan
    • (a) Connect the controlled 2C-24Vac signal from the Exhaust Fan to Adaptor #6 & #7.
    • (b) If using dry contacts, connect one wire to Adaptor terminals #7 and the other wire to furnace terminal ‘C’, and add a Jumper Wire between Adaptor Terminals #5 & #6.
  2. Turn on the power supply to both Furnace and Exhaust Fan. Turn on the Exhaust Fan which will simultaneously turn on the Furnace Circulation Fan

Connecting a replacement Fresh Air Damper (if used) to open simultaneously with either Exhaust Fan running

  • Turn off the power supply to the furnace
  • Install a Hoyme ‘HAC’ 2C-24Vac Motorized Fresh Air Control Damper to the duct as per instructions supplied with it. Satisfactory opera­tion of the damper is recommended before fastening to the Fresh Air Duct
    • (a) For a Power Open Damper, connect one damper wire to Adaptor terminal #1 and connect the other damper wire to the Furnace Terminal ‘C’
    • (b) For a Power Close Damper, connect one damper wire to Adaptor terminal #2 and connect the other damper wire to Furnace Terminal ‘C’
  • Turn on the power supply to the furnace. If the damper is a Power Open type, it will remain closed at this time. If damper is a Power Close type, it will close at this time

If the HAC Fresh Air Damper is to also open during furnace firing:

  • Turn off the main power to the furnace and connect Adaptor terminal #9 to Furnace (W)
  • Turn power on to the furnace and turn the thermostat for the furnace to fire. Damper will open during the firing cycle of the furnace and will close to save energy when the furnace fire stops

Schematic Wiring Diagram of Adaptor
ADP-1103-TW5

Hoyme-ADP-1103-tw5-wiring-diagram2

Note: This marking is also on label to be affixed adjacent to appliance wiring diagram.

Additional wire shall be of the same size as originally used when completing electric circuits.


For more information, please contact HMI Hoyme Manufacturing Inc. @ 1-800-661-7382