Hoyme Colored Wiring Diagram #7A


24Vac Vent Switch, Combustion Air, and Replacement Air with Two Exhaust Fans and Two individual Timers:

#7A. Two 24vac Ventilation Switches/Timers and Two Exhaust Fans, Combustion Air Damper, One Adaptor (ADP-0241-05A), One Power Close Replacement Air Damper (-PC).

HMI Hoyme Manufacturing Inc. Special Note: Circuits are colored for clarification only and are not necessarily those found in actual installations. Combustion Air Damper Wires, however, are colored as shown.

Hoyme-colored-wiring-diagram-7a-image

Diagram #7A: A Forced Air Furnace, a Combustion Air Supply Duct, a Replacement Air Supply Duct, two Exhaust Fans, two individual Timers and an Adaptor ADP-0241-05A.

  1. Combustion Air Damper (HOM-0x11-SF1)
  2. Replacement Air Damper (HAC-0x10-OPC)
  3. Two exhaust fans having individual timers with switching capabilities
  4. 24Vac Relay Adaptor (ADP-0241-05A) to function as a control center

OPERATION:

  1. Combustion Air Damper and Replacement Air Damper open during Furnace firing
  2. Ventilation Switch/Timer (either one) turns on Exhaust Fan(s), opens Replacement Air Damper and turns on Furnace Fan simultaneously
  3. Optional switch (i.e. toggle switch, timer, de-humidistat) allows full control of Replacement Air Damper to open as required provided it is a Power Close type

N.B. Replacement Air Damper is not affected by the ‘Manual’ setting of the Furnace Fan.

Hoyme Colored Wiring Diagram #7A – Printer friendly (pdf)