High Efficiency Forced Air Furnace and a 120Vac Gas Dryer that requires a separate Fresh Air Duct for its operation:
#8A7. Forced Air Furnace with Replacement Air Damper (HAC-0x10-OPC) and MAC Power Close Air Supply Damper (MAC-0x11-SPC) which Supplies Replacement Air For 120vac Gas Dryer using Adaptor (RADP-0241-S10A).
HMI Hoyme Manufacturing Inc. Special Note: Circuits are colored for clarification only and are not necessarily those found in actual installations. Combustion Air Damper Wires, however, are colored as shown.
Diagram #8A7: Forced Air Furnace having a Replacement Air Supply Duct into the return Plenum which provides fresh air for the living area in the home. Also included is a separate Fresh Air Duct for a 120Vac Gas Dryer.
- Fresh Air Damper with Relay and End Switch MAC-0x11-SPC (Power Close)
- 24Vac Relay Adaptor with a Duplex Receptacle Receptacle and a Red Light (on/off) Switch RADP-0241-S10A
- Replacement Air Control Damper HAC-0x10-OPC (Power Close)
OPERATION:
- The MAC Fresh Air Damper is to be open before the Dryer operates. It is interconnected to the Furnace and to the Adaptor RADP-0241-S10A
- The RADP-0241-S10A is plugged into a regular 120Vac outlet and the Gas Dryer is plugged into the RADP-0241-S10A receptacle
- Manually turning on the Red Light Switch opens the MAC Fresh Air Damper which closes the End Switch to turn the red light on. The Damper is thus proven to be open (interlocked) ready for the Dryer to run
- The Replacement Air Damper HAC-0x10-OPC and the Furnace Circulation Fan operate simultaneously when the Red Light Switch is turned on
- After the Dryer cycle is complete, the Red Light Switch may be turned off, causing the Furnace Fan to stop and the Dampers to close
The Optional On/Off Switch will override the HAC Damper to be continually open.
Note: This installation does not interfere with the normal operation of the heating or cooling cycles of the Furnace.