Hoyme Colored Wiring Diagram #8D2


Forced Air Furnace with Combustion and Replacement Air Supply Ducts – Power Close Replacement Air Damper also opens on cooling cycle:

#8D2. Forced Air Furnace with Combustion Air Damper (HOM-0x11-SF1) and a Power Close Replacement Air Damper (HAC-0x10-OPC) that uses Adaptor (ADP-0241-05A) to Open Replacement Air Damper during both Heating and Cooling Cycles and to Open Combustion Air Damper During Furnace firing.

HMI Hoyme Manufacturing Inc. Special Note: Circuits are colored for clarification only and are not necessarily those found in actual installations. Combustion Air Damper Wires, however, are colored as shown.

Hoyme-colored-wiring-diagram-8d2-image

Diagram #8D2: Forced Air Furnace with a Fresh Air Supply Duct for Combustion Air and a Replacement Air Supply Duct.

  1. Combustion Air Damper (HOM-0x11-SF1)
  2. Replacement Air Damper, Power Close (HAC-0x10-OPO)
  3. 24Vac Relay Adaptor (ADP-0241-05A) to operate the Damper on the cooling cycle

OPERATION:

  1. Combustion and Replacement Air Dampers open during Furnace firing
  2. The Power Close (PC) Replacement Air Control Damper also opens on the cooling cycle
  3. Optional switch (i.e. toggle switch, timer, de-humidistat) provides full control of Replacement Air Damper to open as required

N.B. Replacement Air Damper is not affected by the ‘Manual’ setting of the Furnace Fan.

Hoyme Colored Wiring Diagram #8D2 – Printer friendly