HLS – Heat Limit Switch


HMI HLS Series – Heat Limit Switch


HLS-1100 – Heat Limit Switch Information Sheet – Printer Friendly (PDF)

The HMI Hoyme HLS-1100 – Heat Limit Switch

The HLS-1100 Heat limit Switch can be used in conjunction with a regular appliance attached to the Hoyme HOM – Combustion Air Damper without interfering with it’s normal operation.

Hoyme-HLS-heat-limit-switch-1100-and-HOM-and-hot-water-tank
Exhausting stack/Flue vent above Water Heater with Heat limit switch installed. Also pictured is the HOM – Combustion Air Damper

Hoyme HLS-1100 Operational Details:

  • The Heat limit Switch is placed in-line with the source of 24v Power to the Motor of the Damper
  • Usually connected between “R” on the appliance and #5 (blue wire) of the HOM – Combustion Air Damper using regular Thermostat Wire
  • The Heat Limit Switch is normally closed but opens when it reaches 130°F cutting the power to the Damper and causing the Damper to drop open
  • After it has cooled back down to 115°F the switch returns to the closed position and restores power to the motor causing the Damper to also close
Hoyme-HLS-heat-limit-switch-1100Hoyme-HLS-heat-limit-switch-1100-band

Wiring Diagrams used with the HLS-1100:


HLS-1100 – Heat Limit Switch Information Sheet – Printer Friendly (PDF)