Home Support Frequently Asked Questions ...Where is the HOM damper installed?

Where is a HOM damper Installed?

Where is a HOM-Combustion Air Damper Installed?

The HOM - Combustion Air Damper is installed on the terminating end of your combustion air duct which according to the B149 Gas Code should be located within 1 ft above and within 2 ft. horizontally of the largest input appliance.

The following as taken from the B149 Gas Code.

8.3.1
(d) (The duct shall) terminate within 1 ft (300 mm) above, and within 2 ft (600 mm) horizontally from, the burner level of the appliance having the largest input.

Reproduced with permission.


Click here to see more of the Building code.